Comark RF500 Manual de usuario Pagina 34

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 42
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 33
Pinout and Wiring
These connectors are drawn from the point of view of looking into the socket from outside
the transmitter
Door Connector
A Door Positive
B RF525 Activator Positive
C Common Ground for Door and RF525
Lumberg Connector
1
2
3
4
5
6
Pin No RF512 Pinout RF515 Pinout RF516 Pinout
1 Thermistor External-2 External-2 Positive Pt100 Positive Voltage
Input
2 Thermistor External-1 External-1 Positive Pt100 Positive Current
Drive
3 Thermistor External-4
(Reserved for future use)
Reserved for future use
Do Not Connect
No Connection
4 Thermistor Common External Common Pt100 Negative Current
Drive
5 Thermistor External-3
(Reserved for future use)
Reserved for future use
Do Not Connect
Pt100 Negative Voltage
Input
6 No Connection No Connection No Connection
Power Connector
A Positive +5 VDC
B Negative Ground
Gateway Relay Outputs
The two relay outputs each accept a 2.5mm jack plug. These are individually controlled
SPST relay contacts. Comark provide 2 jack plugs for wiring external equipment to be
activated by the Gateway.
Ensure that any external equipment presents only a low voltage on the jack so
as to prevent any chance of personal injury due to electric shock should the jack
plug become disconnected.